Fire alarm audibility: sound levels, ambient measurement and the evacuation signal
A horn passes or fails against the room it is in, not its data sheet. Measure the ambient first, then check the margin, the ceiling and the signal itself.

An audible fire alarm signal is not judged by how loud the horn is on paper. It is judged by whether it stands out over the room it is in. NFPA 72 Chapter 18 sets that test, and most audibility failures trace back to one skipped step: nobody measured the room first.
The margin over ambient
A public mode audible signal has to rise clearly above the ambient sound level. There are two ways to set the margin, and whichever demands more governs:
- A margin over the average ambient level, commonly given as 15 dBA.
- A smaller margin over the loudest sound that persists for a meaningful time, commonly given as 5 dBA above a maximum sound lasting at least 60 seconds.
There is also an upper limit. Total sound pressure anywhere a person can be is capped, commonly given as 110 dBA, so the notification does not become a hazard of its own. Small hard rooms with several horns go over it easily without anyone noticing.
Where the ambient is so high that an audible signal cannot reliably be heard, commonly given as an average at or above 105 dBA, visible notification is required instead.
Measure the ambient, do not guess it
Sustained sounds from normal building operation count toward the ambient. Brief or abnormal sounds do not have to, and the dividing line is commonly given as 60 seconds. A passing truck does not set your design level. A running production line does.
From the field
Guessing the ambient is the reason systems get installed and then fail an audibility test. Measure it.
The evacuation signal
The evacuation signal is the standard three pulse temporal pattern, a recognized pattern that means evacuate, everywhere. A system sounding a steady tone or a march time signal for evacuation is not compliant, and occupants do not understand it.
Where an audible appliance is there to wake somebody in a sleeping room, it has to produce a low frequency signal rather than the standard higher pitched tone. A standard horn in a bedroom does not satisfy this. Low frequency sounders are physically larger and draw more current, so retrofitting them changes the battery calculation and often the circuit loading. The requirement arrived in the 2010 edition for new installations. Whether it reaches an existing system depends on the edition your AHJ has adopted and on what work is being done.
Zones, not floors
NFPA 72 Chapter 23 requires listed notification appliances in each notification zone of a system provided for evacuation or relocation. Where several notification appliance circuits sit in one zone, every appliance in it activates and deactivates together. Zone boundaries follow the outer walls, fire or smoke compartment boundaries, floor separations and other fire safety subdivisions, and they have to match the evacuation plan. A floor is usually a zone, but a floor split by a fire barrier can be two.
Mounting, and where horns are not required
Where the ceiling allows, a wall mounted audible appliance has its top at least 90 in. above the finished floor and at least 6 in. below the ceiling. That is a default, not an absolute. Ceiling mounted and recessed appliances are expressly permitted, a combination audible visual unit follows the visual mounting rules, and other heights are allowed where the sound pressure requirements are still met. Do not write up a ceiling mounted horn against the 90 in. rule.
NFPA 72 does not itself require notification in exit stair enclosures, exit passageways or elevator cars, unless other codes and standards require it. The building code or the life safety code frequently does, so check the adopted code before leaving them out.
From the field
Indoor appliances on a loading dock or in a parking garage fail early and are not listed for it. Appliances for outdoor use, high humidity or exposure to tampering are listed for that application.
Keep reading

Heat detector spacing and temperature ratings under NFPA 72
Pick the rating against the hottest the ceiling gets, keep off the corner, and only halve the spacing in the direction the code says.

Box fill and conduit fill basics for fire alarm work
Box fill counts more than wires, and conduit fill depends on how many conductors are in the pipe. The parts of the count people leave out.

Supervising station monitoring: communication paths and timing
Which kind of station is actually under contract, how fast the signal has to arrive, and why the router in the closet matters as much as the panel battery.

Fire department access: the address, the road, the hydrant, the key box and the FDC
Everything inside the building depends on the fire department getting to it. Five things to check from the street before you walk in.

Manual pull stations: placement, height and travel distance
Measure to the handle, put one by every exit, then walk the floor to check nobody is more than 200 feet from one.

Smoke detector sensitivity testing: measured, not sprayed
Canned smoke proves a detector responds. It does not prove it is in calibration. Here is the schedule, and how the longer interval is earned and lost.