NFPA 72 §17.6 & §17.7

Smoke & Heat Detector Spacing

Detector count on a smooth ceiling, with high-ceiling, beam/joist, and corridor spacing extension.

Enter the room dimensions to see the required detector count.

Nominal smooth-ceiling spacing for smoke detectors is 30 ft unless the listing says otherwise.

Reduces spacing perpendicular to the member: joists by half, beams to two-thirds.

A narrow corridor doesn't need diagonal ceiling coverage the way an open room does, so detectors can sit farther apart along its length and still keep every ceiling point within 0.7 × the effective spacing. This is Annex A guidance in NFPA 72, not a mandatory design method — some AHJs won't accept it, so confirm before using it on a real design.

A necessary note. Spacing rules and the heat-detector ceiling-height table are from NFPA 72 §17.6 (heat) and §17.7 (smoke), cross-checked against a manufacturer detector application guide citing the same sections. Corridor spacing extension uses the 0.7 rule's own point-to-point coverage geometry (extended spacing = 2 × √((0.7 × effective spacing)² − (corridor width ÷ 2)²)), cross-checked against an independent field reference giving 41 ft spacing for a 10 ft wide corridor at 30 ft listed spacing — it is Annex A guidance, not a mandatory rule, and not every AHJ accepts it. This tool assumes ordinary smooth-ceiling or beam/joist conditions on a rectangular room using the grid method — it does not cover sloped/peaked ceilings, high air movement, or performance-based design for high ceilings, all of which need an engineering evaluation per NFPA 72 §17.3. This is a planning aid, not a substitute for a code review by a licensed design professional or your authority having jurisdiction.