Fire extinguisher inspections: the owner's monthly look and the service visit
The monthly check is the owner's job, and it is the one most often not happening at all. What NFPA 10 asks for, from placement to hydro.

Portable extinguishers are the most common piece of fire protection in any building, and the most commonly neglected. NFPA 10 covers which one goes where, how it is mounted, and who checks it how often.
The right extinguisher in the right place
The extinguisher is selected for the hazard actually present, and the hazard classification also drives how far apart they can be (Chapter 5). Travel distance to an extinguisher is capped, and the cap depends on the hazard class and the extinguisher rating (Chapter 6). Measure the walk, not the line of sight.
A kitchen with a cooking grease hazard needs a Class K extinguisher within a short walk of the appliances. It backs up the suppression system. It does not replace it. Where the hazard is protected by an automatic fire protection system, a placard near the extinguisher says to actuate the fixed system before using the extinguisher: the fixed system shuts off fuel and power, and a portable does not.
Mounting and access
Extinguishers are mounted where anyone can lift them down, with the height limit lowered for heavier units and the bottom held clear of the floor. They are visible and reachable, and where one cannot be seen from the space it serves, its location is marked.
From the field
Stored material in front of an extinguisher is the same finding as a blocked pull station, and just as common.
The monthly inspection belongs to the owner
Somebody looks at every extinguisher every month (Chapter 7). It is a quick visual check by the owner or their staff, not a service visit, and it is recorded. It is also the check most often not happening at all.
Beyond the annual
Past the annual service, extinguishers get an internal examination and a hydrostatic test on longer cycles, and the interval depends on the type of extinguisher (Chapters 7 and 8). Carbon dioxide units are the odd one out: they take the 5 year hydrostatic test but are not subject to the 6 year internal examination. Read the table for the type in front of you rather than applying one cycle to the whole wall.
Keep reading

Secondary power and standby batteries: what NFPA 72 asks of them
24 hours quiet, then the alarm. Why the battery calculation matters more than a load test, and why an undated battery is the installer's problem.

Kitchen hood suppression systems: the hazard, the system and the inspection
The grease decides whether a hood needs a system. What happens when it discharges, where the pull goes, and the four changes that force an upgrade.

Changed the system? What NFPA 72 says you retest
One added horn is a one device test. One added horn plus a programming change is not. How the scope of reacceptance follows what changed.

Spot smoke detector spacing and placement: the NFPA 72 basics
A 30 foot grid is where layout starts, not where it ends. The rules that decide whether a corner, a partitioned office or a hidden detector is covered.

Emergency lighting testing: the monthly and annual tests NFPA 101 asks for
The 30 second monthly test, the 90 minute annual, and why a wall of self testing units still needs somebody to look at it.

What goes in a fire alarm drawing package: the NFPA 72 minimum
Floor plans, risers, calcs and the sequence of operation. What Chapter 7 expects on every system, and where it has to live once the job is done.